Mid-mounted cabinet: KYN28A-24
High-voltage Switchgear

Mid-mounted cabinet: KYN28A-24

The 10kV mid-mounted cabinet, officially termed Armored Enclosed Switchgear (AEI), is a core power distribution device in electrical systems responsible for energy reception and distribution. Its name derives from the central placement of the circuit breaker trolley within the cabinet. Widely deployed in industrial and mining facilities, infrastructure projects, and 10kV substations, this equipment performs critical functions including control, protection, monitoring, and isolation.

  • Model KYN28A-24

The product features a highly modular design. Key components such as the circuit breaker and isolation carriage are mounted on a removable cart, enabling flexible operation and easy maintenance through multiple positioning states including working, testing, isolation, and removal. The cabinet is constructed from high-quality aluminum-zinc coated steel plates through multiple bending processes, forming a fully enclosed metal armor structure. It is divided into isolated compartments: busbar room, circuit breaker cart room, cable room, and instrument relay room, ensuring operational safety and preventing fault escalation.
The mid-mounted cabinet features a comprehensive "five-prevention" locking mechanism to prevent accidental operation. Its core specifications typically include a rated current of 1250A to 3150A and a short-circuit breaking capacity of 25kA to 40kA. Optional integrated protection devices enable intelligent measurement and protection. Designed in strict compliance with domestic and international standards such as GB and IEC, this product stands out with high reliability, compact structure, user-friendly operation, and safe maintenance, making it the preferred equipment for modern distribution network construction.

Project‌

Unit‌

numerical value ‌

Rated Voltage

KV

24

Rated Frequency

Hz

50/60

Lightning Impulse Withstand Voltage (Peak)

KV

Phase-to-phase: 60;

Isolation break: 79

1min Power Frequency Withstand Voltage(effective value )

KV

Phase-to-phase:125;

Isolation break: 145

Auxiliary control circuit withstand voltage at power frequency

V

200

Rated Current

A

630,1250,1600,2000,2500,3150

Rated Short-Circuit Interrupting Current

KA

20/31.5

Rated Short-Circuit Closing Current (Peak)

KA

50/80

Rated Short-Time Withstand Current

KA

20/31.5

Rated Peak Withstand Current

KA

50/80

Auxiliary Control Circuit Rated Voltage

V

DC or AC 110/220

Protection Degree

-

IP4X(The circuit breaker room door is open or the compartment is IP2X.)IP4X

External Dimensions (Width×Depth×Height)

MM

800×1810×2380/1000×1810×2380

Weight

Kg

840-1440

Operating Conditions

Ambient temperature range
+40°C to-15°C, with a 24-hour average temperature not exceeding 35°C.
Temperature specifications
Daily relative humidity average ≤95%; monthly relative humidity average ≤90%. Daily water vapor pressure average ≤2.2 KPA; monthly water vapor pressure average ≤1.8 KPA. 
Altitude
≤1000 m. 
Ambient air
Free from significant dust, smoke, corrosive/flammable gases, vapors, or salt spray contamination. 

External vibrations from switchgear and control equipment, as well as ground motion, are negligible.  
Electromagnetic interference (EMI) induced in secondary systems shall not exceed 1.6 KV.