Leave Your Message
AC low voltage distribution cabinet: GCK
Low-voltage Switchgear

AC low voltage distribution cabinet: GCK

The GCK AC low-voltage distribution cabinet is a core equipment for power distribution systems in industrial and mining enterprises as well as high-rise buildings, with a rated voltage of 400V and a rated current up to 6300A. Featuring a modular design, the cabinet boasts a compact structure, rational layout, and convenient installation and maintenance.

  • Model GCK

The main product structure is constructed with premium steel, delivering exceptional mechanical strength and corrosion resistance. Its interior adopts a standardized functional drawer design, featuring flexible drawer operation and high interchangeability for rapid fault isolation and circuit replacement. The busbar system boasts reliable insulation, outstanding thermal stability, and exceptional short-circuit tolerance.
This series of distribution cabinets features a comprehensive five-prevention interlock safety mechanism, effectively preventing misoperation and ensuring both personnel and equipment safety. With an IP40 protection rating, it adapts to various industrial environments. The system can integrate intelligent monitoring units to monitor electrical parameters in real time, issue early warnings for faults, and support automated power system management.
This product is widely used in power generation, substation, petrochemical, rail transit and other places, as power distribution, motor control and lighting distribution. With its high reliability, high safety and flexible configuration scheme, it provides users with stable and efficient power distribution solutions.

Item

Parameter

Rated Operating Frequency (Hz)

50

Rated Operating Voltage (V)

380, 660

Rated Insulation Voltage (V)

600

Rated working current (A)

Horizontal busbar, vertical busbar

630-2500、600 / 630-6300,5300-400

Rated Short-Time Withstand Current (A)

Horizontal busbar, vertical busbar

80kA(effective value)/1s, 50kA(effective value)/1s

100kA(effective value)/1s, 65kA(effective value)/1s

Rated Peak Withstand Current (A)Horizontal busbar, vertical busbar

176KA/0.1s, 110KA/0.1s

220KV/0.1s,145KA/0.1s

Main Circuit Connector (A)

200, 400, 630

Auxiliary Circuit Connector (A)

10

Power Frequency Withstand Voltage 1 Minute (V)

2500

Protection Degree

IP40

Operating Mode

Local, remote, automatic

Operating Conditions

Environmental Temperature
The ambient air - temperature shall not be higher than +40°C, and the average temperature within 24h shall not be higher than +35°C. The ambient air - temperature shall not be lower than - 50°C.
Altitude
The altitude shall not exceed 2000m.
Atmospheric conditions
The air is clean, and the relative humidity shall not exceed 50% at a temperature of +40°C. A higher relative humidity is allowed at lower temperatures, for example, 90% at +20°C.
Installation Site
The product shall be installed in places without fire, explosion hazards, severe pollution, chemical corrosion, and severe vibration.

The product is suitable for transportation and storage at the following temperatures: -25°C to +55°C, and not exceeding +70°C in a short - term (not more than 24h). 
The inclination from the vertical shall not exceed 5°. 
If the above - mentioned usage conditions cannot be met, the user shall put forward the requirements to the manufacturer when placing an order for negotiation and settlement.

Request A Quote